To calculate the make-up water flow rate, determine the evaporation rate using one of the following:
1. The evaporation rate is approximately 2 GPM per 1 million BTU/Hr of heat rejection.
2. The evaporation rate is approximately 3 GPM per 100 tons of refrigeration.
3. Evaporation Rate (GPM) = Water Flow Rate (GPM) x Range (°F) x 0.001.
Multiply the evaporation rate by the appropriate correction factor in the table below to calculate the make-up water flow rate, in GPM.
|
Cycles of |
Correction |
| 2 | 2.00 |
| 3 | 1.50 |
| 4 | 1.33 |
| 5 | 1.25 |
| 6 | 1.20 |
| 7 | 1.17 |
| 8 | 1.14 |
| 9 | 1.13 |
| 10 | 1.11 |